10-34 Testing and Troubleshooting Date Code 20080110
SEL-387E Instruction Manual
Step 14.
Purpose: Display the appropriate Relay Word bit on the front-panel LEDs.
Method: Execute the
TARGET
command (i.e.,
TAR F 59Q <Enter>
). The
SEL-387E Relay now displays the state of the overvoltage elements on
the bottom row of front-panel LEDs.
Step 15.
Purpose: Apply balanced three-phase voltage below the setting and raise one phase
voltage until the appropriate LED illuminates.
Method: Apply balanced three-phase voltages as shown in
Figure 10.5. Raise one
phase voltage until the
59Q
LED illuminates. The negative-sequence
voltage,
V2
, should equal the
59QP
setting ±2 V and ±5% of setting. The
negative-sequence voltage may be calculated as (VA + a
2
VB +aVC)/3
where a = 1 ∠120.
Step 16.
Purpose: Verify the expected residual overvoltage pickup setting.
Method: Execute the
SHOWSET
command via the relay front panel or serial port
and verify the setting (i.e.,
SHO 59G1P <Enter>
).
Step 17.
Purpose: Display the appropriate Relay Word bit on the front-panel LEDs.
Method: Execute the
TARGET
command (i.e.,
TAR F 59G1 <Enter>
). The
SEL-387E Relay now displays the state of the overvoltage elements on
the bottom row of front-panel LEDs.
Step 18.
Purpose: Apply balanced three-phase voltage below the setting and raise one phase
voltage until the appropriate LED illuminates.
Method: Apply balanced three-phase voltages as shown in
Figure 10.5. Raise one
phase voltage until the
59G1
LED illuminates. The residual voltage,
V0
,
should equal the
59G1P
setting
±2 V
and ±5% of setting. The residual
voltage may be calculated as the vector sum (VA + VB +VC)/3.
Step 19.
Purpose: Repeat the test for each residual overvoltage element.
Method: Repeat Steps 16–18 for the
59G2
overvoltage element.
Verify the operation of undervoltage elements.
Step 1.
Connect a source of variable three-phase voltage to the relay as shown in Figure
10.5.
Step 2.
Purpose: Verify the expected phase undervoltage pickup setting.
Method: Execute the
SHOWSET
command via the relay front panel or serial port
and verify the setting (i.e.,
SHO 27P1P <Enter>
).
Step 3.
Purpose: Display the appropriate Relay Word bit on the front-panel LEDs.
Method: Execute the
TARGET
command (i.e.,
TAR F 27P1 <Enter>
). The
SEL-387E Relay now displays the state of the undervoltage elements on
the bottom row of front-panel LEDs.