9
Error and alarm messages
Diagnostics
Fatal error code F1633, error 108, subcode 046
Error message Faulty encoder type range check.
Cause Incorrectly configured encoder type.
Remedy Undo the changes in the encoder configuration or enter new values.
Reload the configuration data. Next switch the DCS..B option off and on again.
If the error still persists, consult SEW Service for the proper MOVISAFE
®
software
version.
Fatal error code F1635, error 108, subcode 047
Error message Faulty encoder scaling range check.
Cause Incorrectly configured encoder distance.
Remedy Undo changes made to the encoder distance (measuring length, resolution or
max. speed) or enter new values.
Reload the configuration data. Next switch the DCS..B option off and on again.
If the error still persists, consult SEW Service for the proper MOVISAFE
®
software
version.
Fatal error code F1637, error 108, subcode 048
Error message Faulty encoder position range check.
Cause Incorrectly configured encoder distance.
Remedy Undo changes made to the encoder distance (measuring length, resolution or
max. speed) or enter new values.
Reload the configuration data. Next switch the DCS..B option off and on again.
If the error still persists, consult SEW Service for the proper MOVISAFE
®
software
version.
Fatal error code F1639, error 108, subcode 049
Error message Faulty PDM range check.
Cause Faulty configuration data of the PDM function.
Remedy Undo the changes in the PDM configuration or enter new values.
Reload the configuration data. Next switch the DCS..B option off and on again.
If the error still persists, consult SEW Service for the proper MOVISAFE
®
software
version.
Fatal error code F2001/2002, error 108, subcode 050/051
Error message Error during internal data transmission.
Remedy Replace the DCS..B option and send it together with error number to SEW Service for
further inspection.
Fatal error code F2003/2004, error 108, subcode 052/053
Error message Error during internal data transmission.
Remedy Replace the DCS..B option and send it together with error number to SEW Service for
further inspection.
Fatal error code F3001/3002, error 108, subcode 054/055
Error message Internal program error.
Remedy Replace the DCS..B option and send it together with error number to SEW Service for
further inspection.