Loading...
Product Description
FLOWSIC100 Flare · Operating Instructions · 8013344/11L2/V 2-5/2018-10 · © SICK Engineering GmbH 37
Subject to change without notice
Type code for sender/receiver units ATEX Zone 1/IECEX and Zone 2 (continued)
Type code for sender/receiver units with certification CSA Cl I, Div1/Div2
pg. 253, § 6.8.
Application area, configurations
1)
: in measuring operation
2)
: when retraction mechanism is being used
3)
: for pipe diameter 300 mm ... 1200 mm (12” ... 48”)
4)
: for pipe diameter >1200 mm ... 1800 mm (> 48” ... 72”)
Versions for low-temperature range -196 ... +100°C on request
Parameter Code Design/Description Type of sender/receiver unit
Miscellaneous
N None
1 Ambient temperature range -50 ... +70°C
2 Tropicalized electronics
3 Offshore painting
4
Offshore (housing/outer parts SS,
standard offshore painting)
5
Offshore (housing/outer parts SS,
standard offshore painting) and
tropicalized electronic
S Special
Type of sender/
receiver unit
Gas temperature
[°C]
Pressure
[barg]
Active measuring
path
[mm]
Pipe diameter
[mm]
NL
[mm]
standard range high temperature range
FLSE100-EXS -70 ... +180 -70 ... +280°C
-70 ... +260°C for zone 2
16 105 ... 620 100 ... 600
(4" ... 24")
148 / 176
FLSE100-EXS
retractable
330
FLSE100-EX -70 ... +280°C
-70 ... +260°C for zone 2
205 ... 1850 200 ... 1800
(8" ... 72")
198 / 226
FLSE100-EXRE 380
FLSE100-EXPR -70 ... +280°C
-70 ... +260°C for zone 2
16 150 (fixed) 300 ... 1800
(12" ... 72")
220
3)
/ 350
4)
FLSE100-EXPR
retractable
16
1)
0.5
2)
400
3)
/ 530
4)
For information about permissible sample gas pressure/temperature range,
see also
pg. 41, Fig. 7,
pg. 42, Fig. 9,
pg. 43, Fig. 11,
pg. 44, Fig. 13.