Chapter 6 Operating Instructions
M4000 Adv., Adv. A/P, Area
58 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 8010797/YT72/2016-02-19
Subject to change without notice
Configurable muting functions
To activate muting, a LOW/HIGH signal change must occur on input C1, before both mu-
ting sensors in the first sensor pair (e.g. A1 and A2) are active. If this is not the case, the
partial blanking function is initiated on the activation of the sensors in the first sensor
pair.
If muting has been initiated, then a HIGH/LOW signal change must then occur on input
C1. If this is not the case, muting cannot be initiated again.
You will find information on the connection and on the possible combinations for the
additional signal C1 in section 6.10 “Combinable muting functions and facilities for
connecting” from page 63.
Device symbol M4000 Advanced (receiver) or M4000 Advanced (A/P), context menu
Open device window, parameter node Muting configuration.
Notes