Resetting safety function and communication settings to factory settings
•
T
he configuration for the safety function is reset to factory settings.
•
The configuration of device communication is reset to factory settings (connec‐
tions for configuration, safety function and data not relating to safety).
Resetting complete settings to factory settings
•
T
he configuration for the safety function is reset to factory settings.
•
The configuration of device communication is reset to factory settings (connec‐
tions for configuration, safety function and data not relating to safety).
•
The Maintenance personnel and Authorized client user groups are deactivated.
•
The password of the Administrator user group is reset to the factory settings.
7.21.4 Managing passwords
Assigning or changing passwords
1.
Establish connection to the device.
2. In the device window under Service, select the User password entry.
3. In the User password dialog box, select the user group.
4. Enter the new password twice and confirm with Transfer to device.
5. When you are prompted to log on, select your user group and enter the corre‐
sponding password.
✓
The new password is valid for the user group immediately.
Reset password
If you have forgotten the password of the Administrator user group, you can reset it with
the assistance of SICK.
1. Request the form for resetting your password from SICK support.
2. Connect to the device in Safety Designer.
3. In the device window under Service, select the User password entry.
4. In the User password dialog box, select the Start process for resetting the password
option.
5. Send the information displayed on the form to SICK support.
✓
You will then receive an activation code.
6. If the device is connected via network: On the display of the device in the relevant
menu, allow the resetting of the password by pressing the OK pushbutton.
7. Enter and confirm the activation code in the field provided in Safety Designer.
✓
The password of the Administrator user group is reset to factory settings
(SICKSAFE). The Maintenance personnel and Authorized client user groups are deac‐
tivated. The configuration is not changed.
7.21.5 Access management
Overview
Y
ou can activate or deactivate interfaces and selected functions as needed.
In the Projected device area, you can see the settings in the project.
When a device is connected, you can see in the Physical device area the configuration in
the device and the status describing the actual behavior of the device.
Older devices may not support all settings.
Functions and settings
Y
ou can activate, deactivate or select the default setting for each function displayed.
The default setting depends on the device and its range of functions.
CONFIGURATION 7
8027909/2023-02-22 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 – EtherNet/IP™
91