Connection
4.11 Wiring the Electronic Module using the Connection Module
ET 200pro distributed I/O system
110 Operating Instructions, 03/2013, A5E00335544-08
Pin assignment on CM IO 8 x M12, CM IO 8 x M12P connection module and
4 DI / 4 DO DC 24V/0.5A electronic module
Table 4- 3 Pin assignment on CM IO 8 x M12, CM IO 8 x M12P connection module and
4 DI / 4 DO DC 24V/0.5A
electronic module
View of circular connector
Terminal
Assignment
Terminal
Assignment X1 to X4 (inputs)
1 24 V encoder supply U
S
(from 2L+)
(is supplied by the ET 200pro to the
connected encoder)
2
Not assigned
3 Ground 2M
4 Input signal DI
0
: Connector X1
Input signal DI
1
: Connector X2
Input signal DI
2
: Connector X3
Input signal DI
3
: Connector X4
5
Functional earth (FE)
Terminal
Pin assignment X5 to X8 (outputs)
1
Not assigned
2
Not assigned
3
Ground 2M
4 Output signal DQ
0
: Connector X5
Output signal DQ
1
: Connector X6
Output signal DQ
2
: Connector X7
Output signal DQ
3
: Connector X8
5
Functional earth (FE)

Table of Contents