Alarm, error and system messages
9.2 PROFINET IO
ET 200pro distributed I/O system
226 Operating Instructions, 03/2013, A5E00335544-08
9.2.5.3
Error types for electronic modules
Error types and remedies
The table below shows the error types for electronic modules.
Table 9- 8 Error types for electronic modules
Error type
Error text
Meaning
Remedy
00001
B
1
D
Short-circuit
Short-circuit to M potential at
encoder line
Short-circuit to M potential at
output line
Short-circuit to P potential or
ground at output line
Load impedance too low
Correct the process wiring
Check encoder or actuator
00110
B
6
D
Cable break
Signal line to encoder or actuator
interrupted
Defective encoder or actuator
Load impedance too high
Correct the process wiring
Replace the encoder or actuator
Use an encoder with higher
impedance
Use an actuator with lower load
00111
B
7
D
Violation of upper limit The value is above the overrange
Correct the module/encoder
tuning
Change the measuring range in
the parameter assignment
01000
B
8
D
Violation of lower limit The value is below the underrange
Correct the module/encoder
tuning
Change the measuring range in
the parameter assignment
01001
B
9
D
Error Internal module error (diagnostic
message on channel 0 applies to the
entire module)
Replace the module
Short circuit to M. The
electronic/encoder supply is short-
circuited to M potential (only for the
PM-O DC 2x24V outgoing module)
Correct the process wiring
10000
B
16
D
Parameter assignment
error
Module not parameterized Correct the parameters
10001
B
17
D
Encoder voltage or load
voltage is missing
Supply voltages missing or too
low
Load voltage supply missing or
too low
Check the supply voltages
Check the load voltage supply
Correct the process wiring
10101
B
21
D
Reference channel
error
Measuring line for compensation
interrupted
Correct the process wiring
Data record DS2 incorrect
Check data record DS2
Timeout for "Dynamic ref. temp."
Send DS2