Mounting
3.5 Mounting the Electronic Module
ET 200pro distributed I/O system
56 Operating Instructions, 03/2013, A5E00335544-08
3.5
Mounting the Electronic Module
Introduction
The electronic module determines the function of the input and output channels. The
connection module is mounted onto the electronic module.
Requirements
The interface module is mounted onto the rack.
All electronic modules must be installed to the right side of the interface module.
The interface module is inserted into the relevant bus module (as delivered).
The connection module may not be installed when you move the electronic module to a
position further on the left side.