Maintenance and service
7.5 Replacing a bus module
ET 200pro distributed I/O system
164 Operating Instructions, 03/2013, A5E00335544-08
7.5
Replacing a bus module
Introduction
The bus module represents the mechanical and electrical link in the modular configuration of
ET 200pro. You may replace a defective bus module. The electronic module/ pneumatic
interface module is supplied installed on the bus module.
Requirements
A bus module may only be disassembled when:
the electronics/encoder supply 1L+ and the load voltage(s) 2L+ of ET 200pro are shut
down, or
the connection module of the interface module has been removed.
The ET 200pro will be out of operation for the duration of this replacement.
Required tools