Maintenance and service
7.7 Updating the interface module firmware
ET 200pro distributed I/O system
170 Operating Instructions, 03/2013, A5E00335544-08
7.7.3
Updating the firmware online (via networks)
Introduction
To update the firmware of the IM 154-4 PN High Feature (6ES7154-4AB10-0AB0), you
require files (*.UPD) containing the latest FW version.
Note
The online update of firmware pertains only to the IM
154-4 PN High Feature interface
module. When an online firmware update is performed, other modules in the station assume
the configured substitute value behavior or become de
-energized.
Requirements
Online firmware updates can be performed in
STEP 7
V5.4 + SP2 or higher.
The interface module of the station to be updated must be accessible online.
The files containing the current firmware versions must be available in the file system of
your programming device or PC. A folder may contain only the files of one firmware
version.
Performing a firmware update
1. Run
STEP 7
and switch to HW Config.
2. Open the station containing the IM 154-4 PN High Feature you want to update.
3. Select the IM 154-4 PN High Feature.
4. Select the menu command
PLC > Update Firmware
.
5. In the
Update Firmware
dialog, select the path to the firmware update files (*.UPD) using
the
Browse
button.
6. After you selected a file, the information in the lower fields of the
Update Firmware
dialog
box shows you the suitable module and firmware version for the file.
7. Click the
Run
button.
STEP 7
checks whether the selected file can be interpreted by the
IM 154-4 PN High Feature and, if so, downloads the file to the interface module. If this
requires changing the operating state of the IM 154-4 PN High Feature, you will be asked
to perform these actions in the relevant dialog boxes. The IM 154-4 PN High Feature then
automatically updates the firmware.
8. Use
STEP 7
(Read CPU diagnostics buffer) to check whether the IM 154-4 PN High
Feature starts up with the new firmware. You can read out the current firmware version in
the module status of the IM 154-4 PN High Feature.