Connection
4.5 Connecting the interface module to a CM IM DP Direct connection module
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
85
4.5.5
Connecting the supply voltages
Required Tools
Screwdriver with 3 mm blade
Requirements
Wiring rules
Screw terminals for the supply
voltages
Connectable conductor cross-sections
of flexible cables
Without wire end
ferrule
0.14 mm to 2.5 mm
2
With wire end ferrule
0.14 mm to 2.5 mm
2
Number of conductors per terminal
1 conductor
Stripped length of the cable insulation
11 mm
Wire end ferrules to DIN 46228 Without insulating
collar
design A, length up to 21 mm
with insulating collar
design E, length up to 12 mm
Connecting the supply voltages
1. Strip the cables to a length of 11 mm, then crimp on the wire end ferrules.
2. Using a 3-mm screwdriver (tightening torque = 0.5 N/m to 0.7 N/m), terminate the supply
cables on terminal X01, and the daisy-chaining cables on terminal X02 (electronic /
encoder supply 1L+, load voltage supply 2L+).
Figure 4-11 Connecting the supply voltage
See also
Terminating and installing the connection module (Page 86)