Maintenance and service
7.4 Replacing an Interface / Power Module
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
163
7.4
Replacing an Interface / Power Module
Introduction
You can replace a defective interface/power module.
Requirements
To replace the interface / power module, shut down the supply voltages 1L+ and 2L+ of
the defective module.
The removal of the connection module of the interface module leads to the failure of
ET 200pro.
The removal of the connection module of the power module leads to the failure of the
corresponding potential group.
Note
PROFIBUS DP: Removing the connection module of the interface module (CM IM)
The bus terminator function may fail if you shut down 1L+ at the first and last ET 200pro
of a bus segment or remove the connection module.
NOTICE
PROFINET IO: Removing the IM 154-4 PN interface module or connection module
After you shut down the 1L+ voltage of an ET 200pro, the integrated switch will also
cause a failure of all downstream ET 200pro stations.
Required tools
Cross-tip screwdriver, size 2
Screwdriver with 3 mm blade
Replacing the interface / power module
1. Remove the four or two screws from the front of the connection module using a crosstip
screwdriver.
2. Remove the connection module from the interface or power module.
3. Unscrew the two screws on the front panel of the interface / power module (top and
bottom right).
4. Remove the interface / power module from the bus module.
5. Reinstall the new interface / power module and the connection module.
6. Switch on the relevant power supplies.

Table of Contents