EasyManua.ls Logo

Siemens ET 200pro - Overview of parameters of the digital electronic modules

Siemens ET 200pro
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital electronic modules
14.9 Overview of parameters of the digital electronic modules
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
375
14.9
Overview of parameters of the digital electronic modules
Parameters of 8 DI DC 24V
Parameters
Value range
Default
Effective range
Diagnostics for short circuit to M
Disable
Enable
Disable Module
Parameters of 8 DI DC 24V High Feature
Parameters
Value range
Default
Effective range
Group diagnostics
Disable
Enable
Disable Module
Hardware interrupt enable
Disable
Enable
Disable Module
Input delay (ms)
0.5
3
15
20
3 Module
Diagnostics: Short-circuit to M 24 V
encoder supply (channels 0 to 7 *)
Disable
Enable
Disable Channel
Diagnostics: Wire break
(channels 0 to 7)
Disable
Enable
Disable Channel
Hardware interrupt at rising edge
(channels 0 to 5)
Disable
Enable
Disable Channel
Hardware interrupt at falling edge
(channels 0 to 5)
Disable
Enable
Disable Channel
* If you use the electronic module with the connection module CM IO 4xM12, channels 4 to 7 are
mapped to channels 0 to 3. A precise channel-specific diagnosis "Short-circuit to M" is not therefore
possible.