Connection
4.15 Connecting the Outgoing Module with the CM PM-O PP Connection Module
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
137
Pin assignment of the push-pull cable connector
View of the push-pull cable connector
Terminal
Assignment X01 OUT/X02 OUT
Electronic/encoder supply and load voltage supply X01
OUT
1
1L+ electronics/encoder supply
2
Ground for electronics/encoder supply 1M
3
2L+ load voltage supply
4
Ground for load voltage supply 2M
5
Functional earth
Electronic/encoder supply and load voltage supply X02
OUT
1
1L+ electronics/encoder supply
2
Ground for electronics/encoder supply 1M
3
2L+ load voltage supply
4
Ground for load voltage supply 2M
5
Functional earth
Connecting the PP cable connector
1. Insert the CM PM-O PP connection module into the PM-O DC 2x24V outgoing module.
2. Press the push-pull cable connector into the associated sockets on the CM PM-O PP
connection module. The connectors must engage. Ensure that the locking mechanism
between the connector and socket is properly applied.
Note
The CM PM
-O PP connection module can only be mounted on the PM-O outgoing
module.
Closing the unused socket
Always cover any unused push-pull sockets with caps in order to achieve degree of
protection IP65, IP66, or IP67.
See also
PM-O DC 2x24V outgoing module (Page 324)