Functions
8.2 PROFINET IO
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
187
The data structures in the data records correspond to the PROFINET IO definitions.
Table 8- 7 Identification data for PROFINET IO
Identification data 0: (data record index AFF0 hex)
The name of the manufacturer is stored
here. (42 dec = SIEMENS AG)
Order number of the module
Serial number (device-specific)
According to hardware version
Indicates the firmware version of the
module.
• SWRevisionPrefix
(1 byte) V, R, P, U, T
• IM_SWRevision_Functional_
Enhancement
(1 byte) 00 - FF hex
• IM_SWRevision_Bug_Fix
(1 byte) 00 - FF hex
• IM_SWRevision_Internal_
Change
(1 byte) 00 - FF hex
IM_REVISION_COUNTER Read (2 byte) - Provides information on parameter
modifications on the module.
0101 hex Provides information on the identification
data version
(0101 hex = version 1.1)
• IM_Version_Major
(1 byte)
• IM_Version_Minor
(1 byte)
IM_SUPPORTED Read (2 byte) 000E hex Provides information on existing
identification data (I&M1 to I&M3)
Maintenance data 1: (data record index AFF1 hex)
IM_TAG_FUNCTION Read/write
- Enter a identifier here that is unique plant-
IM_TAG_LOCATION Read/write
- Define the installation location of the
Maintenance data 2: (data record index AFF2 hex)
IM_DATE Read/write
YYYY-MM-DD HH:MM Enter the installation date of the module
Maintenance data 3: (data record index AFF3 hex)
IM_DESCRIPTOR Read/write
- Enter a comment describing the module.