Alarm, error and system messages
9.1 PROFIBUS DP
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
195
Reactions to a diagnostic alarm in DPV1 mode, depending on parameter settings
Actions initiated by diagnostic alarms:
The diagnostics are reported as diagnostic interrupts.
In DPV1 mode, diagnostic information is also reported when the CPU is in STOP mode.
Once a diagnostic alarm is signaled it is
Entered in the diagnostic frame as a diagnostic block (one interrupt only)
Stored in the diagnostic buffer of the CPU
Entered in the channel-specific diagnostic data
The SF LED of the interface module and, if applicable, on the affected electronic module
is lit.
OB 82 is called. If OB 82 is not available, the CPU goes to STOP.
Acknowledgment of the diagnostic interrupt The enables a new interrupt.
Reactions to a diagnostic alarm in DPV0 mode, depending on parameter settings
The error is entered in the channel-specific diagnostic information in the diagnostic frame:
The SF LED of the interface module and, if applicable, on the affected electronic module
is lit.
There can be more than one diagnostic alarm at a given time.