Alarm, error and system messages
9.1 PROFIBUS DP
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
207
Error type
Error text
Meaning
Remedy
10001
B
17
D
Encoder voltage or load
voltage is missing
Supply voltages missing or too
low
Load voltage supply missing or
too low
Check the supply voltages
Check the load voltage supply
Correct the process wiring
10101
B
21
D
Reference channel
error
Measuring line for compensation
interrupted
Correct the process wiring
Data record DS2 incorrect
Check data record DS2
Timeout for "Dynamic ref. temp."
Send DS2
10110
B
22
D
Process interrupt lost ET 200pro failed to detect a process
interrupt
Correction or coordination of the
program, process, module
11010
B
26
B
External error
Error at encoder circuit
Correct the process wiring