Alarm, error and system messages
9.2 PROFINET IO
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
217
Status and error displays GE, BF, ON, LINK, RX/TX, FO
Table 9- 3 Status and error displays of IM 154-4 PN High Feature
Off Off On
IO device is currently exchanging data with the
IO controller without errors. The interface
module is supplied with power
-
Off Off Off Electronic/encoder supply missing or too low
Switch
on the electronic/encoder power supply
for the IO device.
Replace the interface module.
* Flashing On Incorrect or no connect frame - no data
exchange is occurring between the
IO controller and the interface module
(IO device).
Causes:
• Incorrect device name
• Configuration error
• Parameter assignment error
• Check the interface module.
• Check the configuration and
parameterization.
• Check the device name.
* On On No IO controller on bus
Causes:
• No bus communication
• Connect to the IO controller.
• Assign a valid device name to the interface
module.
• Check the bus configuration.
• Check whether the M12 cable connectors
are properly installed.
• Check whether the bus cable to the
IO controller is interrupted.
On * On The preset configuration of ET 200pro does
not match the actual ET 200pro configuration.
Check the ET 200pro configuration to see
whether a module missing or defective, or
whether a non-configured module is inserted.
Check the configuration (using STEP 7, for
example), and correct any parameter
assignment errors.
I/O module error or defective interface module.
Replace the interface module, or contact your
Siemens representative.