Connection modules
11.2 Connection modules for the interface module with PROFINET IO
ET 200pro distributed I/O system
258 Operating Instructions, 03/2013, A5E00335544-08
Dimensions W x H x D (mm)
• 1L+ electronics/encoder supply
Max. 16 A*, up to 40 °C ambient temperature
Max. 8 A*, up to 55 °C ambient temperature
• 2L+ load voltage supply
Max. 16 A*, up to 40 °C ambient temperature
Max. 8 A*, up to 55 °C ambient temperature
* Observe the permitted current carrying capacity of the cable.
Note
Feed current
The load on the internal busbars of ET
200pro must not exceed the following values:
At 1L+ 5 A
At 2L+ 10 A