EasyManua.ls Logo

Siemens ET 200pro - Page 440

Siemens ET 200pro
545 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
15.11 Measuring ranges of the analog input modules in S7 format
ET 200pro distributed I/O system
440 Operating Instructions, 03/2013, A5E00335544-08
Current measuring range: 0 to 20 mA
Measuring range
0 mA to 20 mA
Units
Range
Decimal
Hexadecimal
> 23.52 mA
32767
7FFF
H
Overflow
23.52 mA
32511
7EFF
H
Overrange
27649
6C01
H
20 mA
27648
6C00
H
Nominal range
15 mA
20736
5100
H
723.4 nA
1
0001
H
0 mA
0
0000
H
- 1
FFFF
H
Underrange
-3.52 mA
-4864
ED00
H
< -3.52 mA
32768
8000
H
Underflow
Current measuring range: 4 to 20 mA
Measuring range
4 mA to 20 mA
Units
Range
Decimal
Hexadecimal
> 22.81 mA
32767
7FFF
H
Overflow
22.81 mA
32511
7EFF
H
Overrange
27649
6C01
H
20 mA
27648
6C00
H
Nominal range
16 mA
20736
5100
H
4 mA + 578.7 nA
1
0001
H
4 mA
0
0000
H
- 1
FFFF
H
Underrange
1.185 mA -4864 ED00
H
< 1.185 mA
32767
7FFF
H
Wire break
-32768
8000
H
Underflow

Table of Contents

Related product manuals