Analog electronic modules
15.11 Measuring ranges of the analog input modules in S7 format
ET 200pro distributed I/O system
442 Operating Instructions, 03/2013, A5E00335544-08
Measuring ranges for Pt x00 standard thermal resistor
Pt x00 Standard
in °C
(1 digit = 0.1 °C)
Units
Pt x00 Standard
in °F
(1 digit = 0.1 °F)
Units
Range
Decimal
Hexadecimal
Decimal
Hexadecimal
> 1000,0
32767
7FFF
H
> 1832,0
32767
7FFF
H
Overflow
1000,0
:
850,1
10000
:
8501
2710
H
:
2135
H
1832,0
:
1562,1
18320
:
15621
4790
H
:
3D05
H
Overrange
850,0
:
-200,0
8500
:
-2000
2134
H
:
F830
H
1562,0
:
-328,0
15620
:
-3280
3D04
H
:
F330
H
Nominal range
-200,1
:
-243,0
-2001
:
-2430
F82F
H
:
F682
H
-328,1
:
-405,4
-3281
:
-4054
F32F
H
:
F02A
H
Underrange
< -243,0
-32768
8000
H
< -405,4
-32768
8000
H
Underflow
Measuring ranges for Pt x00 climatic thermal resistor
Pt x00 climatic
in °C
(1 digit = 0.01 °C)
Units
Pt x00 climatic
in °F
(1 digit = 0.01 °F)
Units
Range
Decimal
Hexadecimal
Decimal
Hexadecimal
> 155,00
32767
7FFF
H
> 311,00
32767
7FFF
H
Overflow
155,00
:
130,01
15500
:
13001
3C8C
H
:
32C9
H
311,00
:
266,01
31100
:
26601
797C
H
:
67E9
H
Overrange
130,00
:
-120,00
13000
:
-12000
32C8
H
:
D120
H
266,00
:
-184,00
26600
:
-18400
67E8
H
:
B820
H
Nominal range
-120,01
:
-145,00
-12001
:
-14500
D11F
H
:
C75C
H
-184,01
:
-229,00
-18401
:
-22900
B81F
H
:
A68C
H
Underrange
< -145,00
-32768
8000
H
< -229,00
-32768
8000
H
Underflow