Analog electronic modules
15.11 Measuring ranges of the analog input modules in S7 format
ET 200pro distributed I/O system
446 Operating Instructions, 03/2013, A5E00335544-08
Measuring range for type R, S thermocouple
Type R, S
in °C
Units
Type R, S
in °F
Units
Type R, S
in K
Units
Range
Decimal
Hexadeci
mal
Decimal
Hexadeci
mal
Decimal
Hexadeci
mal
> 2019,0
32767
7FFF
H
> 3276,6
32767
7FFF
H
> 2292,2
32767
7FFF
H
Overflow
2019,0
:
1768,1
20190
:
17681
4EDE
H
:
4511
H
3276,6
:
3216,3
32766
:
32163
7FFE
H
:
7DA3
H
2292,2
:
2042,3
22922
:
20423
598A
H
:
4FC7
H
Overrange
1768,0
:
-50,0
17680
:
-500
4510
H
:
FE0C
H
3216,2
:
-58,0
32162
:
-580
7DA2
H
:
FDBC
H
2042,2
:
223,2
20422
:
2232
4FC6
H
:
08B8
H
Nominal
range
-50,1
:
-170,0
-501
:
-1700
FE0B
H
:
F95C
H
-58,1
:
-274,0
-581
:
-2740
FDBB
H
:
F54C
H
223,1
:
103,2
2231
:
1032
08B7
H
:
0408
H
Underrange
< -170,0
-32768
8000
H
< -274,0
-32768
8000
H
< 103,2
-32768
8000
H
Underflow
Measuring range for type T thermocouple
Type T in
°C
Units
Type T in °F
Units
Type T in K
Units
Range
Decimal
Hexadeci
mal
Decimal
Hexadeci
mal
Decimal
Hexadeci
mal
> 540,0
32767
7FFF
H
> 1004,0
32767
7FFF
H
> 813,2
32767
7FFF
H
Overflow
540,0
:
400,1
5400
:
4001
1518
H
:
0FA1
H
1004,0
:
752,1
10040
:
7521
2738
H
:
1DC1
H
813,2
:
673,3
8132
:
6733
1FC4
H
:
1AAD
H
Overrange
400,0
:
-270,0
4000
:
-2700
0FA0
H
:
F574
H
752,0
:
-454,0
7520
:
-4540
1D60
H
:
EE44
H
673,2
:
3,2
6732
:
32
1AAC
H
:
0020
H
Nominal
range
< -270,0 -32768 8000
H
< -454,0 -32768 8000
H
< 3,2 -32768 8000
H
Underflow

Table of Contents