Connection
4.3 Electrical Configuration of ET 200pro
ET 200pro distributed I/O system
76 Operating Instructions, 03/2013, A5E00335544-08
ET 200pro configuration with CM IM PN PP FO connection module
The figure below shows the electrical potentials of an ET 200pro configuration with a
CM IM PN PP FO connection module on the IM154-4 PN High Feature interface module
(6ES7154-4AB10-0AB0).
Figure 4-6 ET 200pro configuration with CM IM PN PP FO connection module
Line protection is required in accordance with DIN VDE 0100, in other words you always
need to provide external fusing:
● Interface module:
Protection of the 1L+ electronics/encoder supply with
miniature circuit-breaker
24 V DC/16 A
, tripping characteristic type B or C.
● Interface module/integrated power module, and power module:
Protection of the 2L+ load voltage supply with
miniature circuit-breaker 24 V DC/16 A
,
tripping characteristic type B or C.
-breaker 24 V DC/16 A with tripping characteristics type B trips
the equipment fuse is tripped.
-breaker 24 V DC/16 A with tripping characteristics type C trips
the
equipment fuse trips.