Connection
4.8 Connecting the IM 154-4 PN High Feature interface module with CM IM PN M12, 7/8"
ET 200pro distributed I/O system
98 Operating Instructions, 03/2013, A5E00335544-08
Connecting M12 and 7/8" cable connectors
1. Press the M12 and 7/8" cable connectors into the corresponding circular socket
connectors of the CM IM PN M12, 7/8" connection module. Ensure that the locking
mechanism between the connector and socket is properly applied.
2. Tighten the knurled screws of the connectors (torque = 1.5 Nm).
Figure 4-14 Connecting M12 and 7/8" cable connectors
Removing the 7/8" cable connector
It is not permissible to remove the 7/8" cable connectors while ET 200pro is in operation!
Always switch off the 1L+ electronics/encoder supply and the 2L+ load voltage supply
before you pull or plug the 7/8" cable connector.
Note
If you remove the M12 or 7/8" cable connector used for forwarding,
downstream modules
on PROFINET IO will fail or will no longer be supplied with power.
Always close all unused sockets using M12 and 7/8" caps in order to achieve degree of
protection IP65, IP66 or IP67.