Operation
Settings / Administration
5
105 |
184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015
12
-
15
'Delete PIN'
ϖ PIN is present.
ϖ You have the required authorization level.
1. Select 'Main menu' > 'Settings/administration' > 'Manage PINs'.
2. Select 'Delete PIN'.
3. Enter the PIN in accordance with the input fields and confirm with <ok>.
PIN has been deleted.
Delete PIN
Enter PIN: ****
Verify PIN: ****
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
5.27.3 Setting the buzzer sound level
You can set the sound level of the 'Station' buzzer on four levels or switch it off.
NOTICE
Buzzer volume too lo
w
Non-compliance with EN 54-2 Para 12.10.2
Set the buzzer sound level to the maximum.
As per EN 54-2, the minimum sound level at a distance of 1 m must reach the
following values, measured under open air conditions:
-60 dB (A) for announcing fire alarm signals
-50 dB (A) for announcing fault messages
'Set buzzer volume'
1. Select 'Main menu' > 'Settings/administration' > 'Set buzzer volume'.
The 'Set buzzer volume' window is open.
2. Select the desired settings in the list.
The buzzer sound level has been set.

Table of Contents

Other manuals for Siemens FT724

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FT724 and is the answer not in the manual?

Siemens FT724 Specifications

General IconGeneral
BrandSiemens
ModelFT724
CategoryControl Panel
LanguageEnglish

Related product manuals