Operation
ALARM Procedure
5
40 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015
12
15
5 Operation
In this part of the document you will find brief descriptions and detailed operation
sequences for important functions of the fire detection installation. In addition, you
can find your preferred procedures in the representation of exemplary operation
sequences.
Certain commands on the fire con
trol panel can only be executed by the service
technician or someone with access level 3. You will find a description of these
specific commands in document A6V10210416. See chapter 'Applicable
documents'.
5.1 ALARM Procedure
System without delayed alarm transmission (AVC)
If your fire detection system has no delayed alarm transmission function ('AVC),
the variant 'Fire Brigade in' 'mm:ss' in Step 2 (see below) does not apply.
1 <Acknowledge> 5 <Alarm device>
2 Top line on the display A <Alarm delay off>
3 <Softkey 2> 'Show intervention text' if displayed R <Reset>
4 Indication of the fire location on the display