System description
Topology
9
138 | 184
Building Technologies
A6V10211076_
i_en_
--
Fire Safety
2015
12
15
9.2.4 Operating tree
The following elements and settings are represented in the Operation tree:
Global system configuration
Display and operator units such as:
Person Machine Interface (PMI)
Floor repeater terminal and floor repeater display
Mimic display
Event printer
Global system configuration
The global system configuration has the following elements:
Global behaviour
Events (event configuration)
Commands ('Access level' assignment)
The behavior set here is always valid unless a different behavior is set locally.
Master clock: The master clock is automatically assigned to the first station
(address 1).
Country settings: Settings are undertaken here for localization and changing
between summer and winter time.
Person Machine Interface (PMI)
The PMI is a permanent part of the station. The following settings can be
configured in the Operation tree:
Basic settings with definition of default access level for the key switch and time
period during which the display returns to the normal display from an operating
display.
Visibility:
A detailed description of the visibility can be found in the corresponding
chapter.
Standard visibility
Standby visibility
Expanded visibility
LEDs for signaling events and statuses (causes):
Event with defined, local visibility.
Event with optional, global visibility on a particular element from the
Hardware tree, Detection tree, or Control tree.
Standard keys:
Frequently used functions can be assigned to the configurable standard keys.
Views, e.g. message indicator, customer text view, fire brigade view
Commands, e.g. activate/deactivate, test, configuration ('Set PS MANNED',
'Switch to UNMANNED', etc.).
Favorite keys:
The favorite keys are in the display menu. There is a maximum of eight favorite
keys of which three are preconfigured. Frequently used functions can be
assigned to the favorite keys.