Operation
Testing
5
75 |
184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015
12
-
15
5.12.2 Carrying out an installation test
As in the 'Installation test' all functions of the complete fire detection installation
including the 'Fire control' and alarming are tested, you must take appropriate
actions.
The 'Installation test' can be carried out at 'Area' or 'Section levels.
WARNING
During the system test, the alarming and fire control are activated!
Personal injury resulting from extinguishing activation
The fire brigade is called up unnecessarily.
Set the 'Fire controls' to 'Control test' in advance.
Inform the fire brigade in advance.
Before the '
Installation test
' you can set '
Fire controls
' to '
Control test
'.
No activation of manual call point zones
Manual call point zones are not activated in the 'Installation test'. The 'Installation
test' is not available for manual call point zones.
Testing the site
Proceed as with 'Detector test' and select the 'Installation test' function.
5.12.3 Carrying out the walk test
κ Proceed as with 'Detector test' and select the 'Walk test' function.

Table of Contents

Other manuals for Siemens FT724

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FT724 and is the answer not in the manual?

Siemens FT724 Specifications

General IconGeneral
BrandSiemens
ModelFT724
CategoryControl Panel
LanguageEnglish

Related product manuals