System functions
Isolation
6
116 | 184
Building Technologies
A
6V10211076_i_en_
--
Fire Safety
2015
12
15
6.6 Isolation
You can switch off 'Zones' with automatic or non-automatic detectors in special
situations, e.g., during construction work.
When parts of the fire detection installation are switched off, the fire detection
installation is in 'ISOLATION' condition and operation mode.
The 'ISOLATION' LED on the Person Machine Interface is on.
In 'ISOLATION' operation mode neither 'ALARMS' nor 'Faults' from the parts of the
site that have been switched off can be evaluated.
You can set isolations with or without a time limit.
See also
1 Switching off / Switching on [ 45]
6.7 Renovation
In the ' --Renovation mode' operation mode, the detector parameter sets are
changed as follows:
No evaluation possible by the optical part of the detector.
A static evaluation by the thermal part of the detector is possible, however,
without the evaluation of the temperature difference.
The '
ISOLATION
' LED on the
PMI is on as soon as a part of the
site has
been set to ' --Renovation mode'.
6.8 Access level and access rights
The 'Station' is protected against unauthorized operation by the following access
levels:
Access level Access rights Functions and access rights
1 Everybody 'Acknowledge' and scrolling
2,1 Operator 1 Limited access rights (e.g. janitor)
2,2 Operator 2
Extended access rights (e.g. safety and
security manager)
3 Service technician All access rights (for service technicians)
On access level 1 the most important commands can be entered in case of
alarm.
Other commands or the configuration of the 'Station' are possible starting
with access level 2,1.
Access levels are enabled by the PIN input dialog or the key switch.
Each PIN is assigned to an access level.
Menu entries, functions and favorites that are not accessible on an access level
are hidden.
You will find a list of all commands and the required access levels in the relevant
chapter.

Table of Contents

Other manuals for Siemens FT724

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FT724 and is the answer not in the manual?

Siemens FT724 Specifications

General IconGeneral
BrandSiemens
ModelFT724
CategoryControl Panel
LanguageEnglish

Related product manuals