Page #136 background image
System description
Topology
9
136 | 184
Building Technologies
A6V10211076_
i_en_
--
Fire Safety
2015
12
15
'Zone': Reset behavior of the manual call points
The reset behavior of an activated manual call point can be selected:
'ALARM' can always be reset; 'Glass broken' is indicated.
or
'ALARM' cannot be reset.
Blocking of the isolation
If the isolation blocking function has been configured, the 'Zone' cannot be
switched off.
'Detector test' timeout
After the expiry of a configurable delay the system automatically cancels
the 'Detector test' state. This function can be deactivated.
Switching devices back on
When devices are switched back on, they are in an undefined state for a
short period. The 'Station' changes to the 'Not ready' state for this
timespan.
Simulation function
With the simulation function the 'Zone' switches from the normal operation
mode to 'Pre-ALARM' and then to 'ALARM'. The controls are activated as if
the detectors had triggered an 'ALARM'. Reset is performed by means of
the keys on the PMI.
9.2.3 Control tree
The Control tree represents the control in the fire detection system. control
groups are grouping units for configuration and operation.
Control groups in 'Control tree'
'Alarming control group'
'Fire control group'
'Evac control group'
'Counter control group'
Each control group has one or more elements, each of which includes an input
(Cause) and an output (Effect).
Elements of the 'Alarming control group' are controls for internal and external
alarm devices
Remote transmission outputs for 'Fire' and 'Fault'
Eight more remote transmission outputs
Elements of 'Fire control group' are controls for building equipment.
Elements of 'Evac control group' are controls for alarm and announcement
devices.

Table of Contents

Other manuals for Siemens FT724

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FT724 and is the answer not in the manual?

Siemens FT724 Specifications

General IconGeneral
BrandSiemens
ModelFT724
CategoryControl Panel
LanguageEnglish

Related product manuals