Maintenance recommendation
11
175 |
Building Technologies
11 System maintenance
Regular maintenance of the ↑ 'Site' is necessary in order to ensure the system will
function reliably.
The fire detection installation has a reminder function that informs you of imminent
maintenance. When the service reminder is displayed, regular maintenance by the
service technician is required.
Depending on national regulations, the maintenance intervals can be set
differently from the following maintenance recommendation.
11.1 Maintenance recommendation
You will find detailed instructions for maintaining the ↑ site in document
A6V10210416.
Please adhere to the local provisions.
Carry out the recommended maintenance work at regular intervals or have it
carried out by a service engineer.
Maintenance work Interval
Testing detectors Annually
Testing the control panel Annually
Simulating alarm Annually
Simulating fault Annually
11.2 Opening the control panel [DE]
It is possible that the housing of the control panel may have to be opened for
maintenance work.
If a class 3 key safe (fire brigade key safe, FSD) forms part of the fire detection
installation, the door contact kit FCA2009-A1 must be installed in the housing of
the control panel.
The door contact kit triggers a 'Sabotage ALARM' if the cover cap is removed from
the control panel.
NOTICE
ALARM by opening the control panel
Measures for 'Sabotage ALARM' are triggered unnecessarily.
Switch off sabotage evaluation before you open the control panel.
See also
1 Switching off sabotage evaluation [DE] [➙ 57]