5.12.1 Testing detectors
The 'Detector test' is a hardware function test for the devices and their assignment
to 'Detection tree'.
The 'Detector test' function can be carried out on the levels 'Zone', 'Section' or
'Area'.
The '
Detector test
' is available for all detector zone types.
Testing all automatic 'Detectors'
1. Select 'Main menu' > 'Functions'.
The 'Functions' menu is open.
2. Select 'Test'.
The 'Select element category' window is open.
3. Select the 'Element category' 'Area'.
The 'Enter address' window is open.
4. Press <ok> without entering an address.
The 'Select command' window is open.
5. Select 'Non-MCP zones det.test'.
All automatic 'Detectors' are set to 'Detector test'.
The 'DETECTOR TEST' LED on the Person Machine Interface is on.
6. Test the 'Detectors'.
Example of selecting commands for the 'Detector test' of all
automatic 'Detectors':
Select command
Installation test
Non-MCP zones det.test END
Installation test END
MCP zones det.test END
Non-MCP zones det.test
(2)
(3)
(4)
(5)
(6)
Ending the Detector test of all automatic 'Detectors'
Proceed as with Detector test but select the 'Non-MCP zones det.test END'
command.