System description
Overview
9
130 | 184
Building Technologies
A6V10211076_
i_en_
--
Fire Safety
2015
12
15
Evaluation of the system events
The fire control panel has comprehensive monitoring and self-monitoring functions.
Deviations from the normal operation mode are recognized as a system event.
System events are allocated to the following event categories:
Event category for system
events
Typical example Activation/cause
'Fault' Faulty detector line
Mains failure detector
Short-circuit, open line or
malfunction
'Isolation' A detector zone has been switched off Operation or control
'Test' A detector zone is switched to Test Operation
'Technical message' Fault or danger from extraneous equipment Sensor or contact
'Activation' A control is activated Operation or control
'Information' Access level
'Manned operation' operation mode
State
Table 7: Event categories for system events
Alarming
The different fire alarms and system events are verified independently from one
another. Depending on the configuration, local alarming or direct or delayed global
alarming is actuated.
Local alarming:
Local alarming equipment (e.g., acoustic or optical alarm devices) is
actuated in order to call up immediately available intervention personnel
(e.g., in-house staff) and to alert people of a possible fire hazard.
Global alarming:
Global alarming equipment (e.g. remote transmission) is actuated and external
intervention forces (e.g. the fire brigade) are alerted.
The following points influence the type of alarming:
Configuration of the alarming process
Position of 'Manned operation'/'Unmanned operation' operation mode
'Manned operation': Personnel present on site
'Unmanned operation': No personnel present on site
Type of alarm activation (automatic or manual)
Control
In the event of fire it makes sense to initiate first, decisive actions automatically.
Automatic measures are carried out by controls, e.g., by the control of building
services, evacuation or extinguishing.

Table of Contents

Other manuals for Siemens FT724

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FT724 and is the answer not in the manual?

Siemens FT724 Specifications

General IconGeneral
BrandSiemens
ModelFT724
CategoryControl Panel
LanguageEnglish

Related product manuals