System description
Topology
9
133 |
184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015
12
-
15
9.2.2.1 Elements of the detection tree
'Area'
'Area' typically corresponds to a building.
'Area' combines 'Sections' which are subject to the same 'Manned
operation'/'Unmanned operation' operation mode.
'Area' actuates the alarming equipment (acoustic and optical alarm devices
as well as remote transmission).
'Area' is assigned the following functions:
'Manned operation'/'Unmanned operation' operation mode
Switching assigned 'Sections' on/ off
Several 'Areas' are possible per control panel:
FC722, FC723, FC724: up to four 'Areas'
FC726 up to eight 'Areas'
There is an 'Area' that groups together the functions of alarm verification (AVC),
e.g. collective alarms and degraded mode operation.
'Section'
'Section' combines 'Zones' to form logical units. Such a unit can be e.g. a floor
or a staircase.
'Section' is assigned the following function:
Switching assigned 'Zones' on/ off
'Zone'
'Zone' generally combines the detectors in a room.
'Zone' evaluates the danger levels transmitted by the detectors. The configured
combination of different danger levels defines the conditions upon which an
'ALARM' is triggered.
The following fire alarm zone types exist:
'Automatic zone'
'Manual zone'
'Technical zone'
'FSE zone'
'Flow switch zone' (sprinkler)
'Sub-system zone'
The following extinguishing zone types exist:
'Sprinkler zone'
'XC10 zone'
'Channel'
The 'Channel' in 'Detection tree' represents the functionality of the inputs and
outputs of an C-NET device.