Operation
Switching off / Switching on
5
46 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015
12
15
Switching off a detector zone
1. Select 'Main menu' > 'Functions'.
The 'Functions' window is open.
2. Select 'On / Off'.
A list of all element categories on which a command of the 'On / Off'
command group can be executed is indicated.
3. Select the 'Element category' 'Zone'.
The 'Enter address' window is open.
4. Press <ok> without entering an address.
All 'Zones' are displayed.
5. Select a 'Zone' and press <'Execute Commands>.
The 'Select command' window is open.
6. WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! Select the 'OFF' command and confirm
with <ok>.
The window with the command response confirms the selected command.
'Zone' is switched off.
Exemplary representation of the aforementioned operation sequence for
switching off a detector zone:
Functions
Exit with <C>
Access level 2.1
On / Off
Test
Activate / Deactivate
Information
(1)
(2)
(3)
(4)
Configuration
Maintenance
Reports
All functions
(5)
(6)
(7)
(8)
Message summary Event memory LED
test
κ Select 'On / Off', continue with <ok>
Selecting element category
Zone
Area
Section
Sounder
Fire control group
(1)
(2)
(3)
(4)
(5)
κ Select 'Zone', continue with <ok>