5. Evaluate your drive response.
If the motor decelerates too slowly, then reduce the ramp-down time.
The minimum ramp-down time that makes sense depends on your particular application.
Depending on the Power Module used, for an excessively short ramp-down time, the
converter either reaches the motor current, or the DC link voltage in the converter
becomes too high.
Extend the ramp-down time if the motor is braked too quickly or the converter goes into
a fault condition when braking.
6. Repeat steps 1 5 until the drive behavior meets the requirements of the machine or plant.
You have set the extended ramp-function generator.
Changing the ramp-up and ramp-down times in operation
The ramping up and down time of the ramp-function generator can be changed during
operation. The scaling value can come, e.g. from the 󹪝eldbus.
Requirements
You have commissioned the communication between the converter and the control system.
Free telegram 999 has been set in the converter and in your higher-level control system.
Expanding or freely interconnecting telegrams (Page228)
The control sends the scaling value to the converter in PZD3.
Procedure
1. Set p1138 = 2050[2].
This means that you have interconnected the scaling factor for the ramp-up time with PZD
receive word3.
2. Set p1139 = 2050[2].
This means that you have interconnected the scaling factor for the ramp-down time with PZD
receive word3.
The converter receives the value for scaling the ramp-up and ramp-down times via PZD
receive word3.
Further information is provided on the Internet:
FAQ (https://support.industry.siemens.com/cs/ww/en/view/82604741)
Advanced commissioning
8.18Setpoint processing
SINAMICS G120C Converters
288 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C DP and is the answer not in the manual?

Siemens SINAMICS G120C DP Specifications

General IconGeneral
Protection RatingIP20
Frequency Range0 to 650 Hz
Control ModesV/f, sensorless vector control
Communication InterfacesPROFIBUS DP
Ambient Temperature-10 to +50 °C (without derating), -10 to +60 °C (with derating)
Overload Capacity150 % rated current for 60 s, 200 % rated current for 3 s
Storage Temperature-40 to +70 °C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V (±10%), 380 V to 480 V (±10%)
Output Voltage0 V to Supply Voltage

Related product manuals