6.5.29 SecureDisplay version [secureDisplayVersion]
For applications requiring official calibration, the "SecureDisplay" software is used to display
the calibratable weight value. The parameter defines the version of the "SecureDisplay"
software that is running in the HMI device. If the version is not entered correctly, a weight value
will not be output in "SecureDisplay", and the display stays in the "Start Up" step.
6.5.30 Smallest zoom factor of SecureDisplay (%)
[smallestZoomFactorOfSecureDisplay]
The minimum display size defines the smallest zoom factor for the "SecureDisplay" calibratable
display. If the parameter does not match the smallest zoom factor in the .xml file in the HMI
device, "SecureDisplay" remains in the "StartUp "step and no weight value is output.
6.6 DR04 Calibration curve check
Calibration digits are calculated based on the parameters from DR10.
The theoretical calibration digits are compared with the measured calibration digits in DR03.
The deviations are output in DR04 as percentages.
6.7 DR05 Tare and zero memory
Current preset-tare weight [presetTareWeight]
Current semi-automatic tare weight [semiAutomaticTareWeight]
Current initial zero-setting weight [initialZeroSettingWeight]
● If you have enabled initial zero-setting in DR03, the current weight is displayed after the
supply voltage is switched on. Initial zero-setting [initialZeroSetting] (Page 63)
Current semi-automatic zero-setting weight [semiAutomaticZeroSettingWeight]
● If you have enabled the automatic zero-setting device in DR03, the current weight of the
zero-setting device is displayed. Automatic zero tracking in dosing cycle
[automaticZeroTrackingInCycle] (Page 65)
Current zero tracking weight [zeroTrackingWeight]
Dead load (calculated) [calculatedDeadLoad]
Theoretically calculated load of the scale construction or the empty scale.
Parameter assignment/addressing
6.7 DR05 Tare and zero memory
Technology module TM SIWAREX WP351 HF
70 Operating Instructions, 01/2020, A5E47521010-AA