Article number 7MH4138-6BA00-0CU0
● IEC 61131-2:2017
● IEC 60068-2-6:2007
● Test Fc
5 ... 8.4 Hz: 3.5 mm out.
8.4 to 150 Hz: 9.8 m/s
2
(= 1 G)
Shock load during operation
● IEC 61131-2:2017
● IEC 60068-2-27:2008
● Test Ea
150 m/s
2
(approx. 15 G), half sine
Duration: 11 ms
Vibration load during transport
● IEC 60068-2-6:2007
● Test Fc
5 ... 8.4 Hz: 3.5 mm Exh.
8.4 ... 500 Hz: 9.8 m/s²
Shock load during transport
● IEC 60068-2-27:2008
● Test Ea
250 m/s
2
(approx. 25 G), half-sine
Duration: 6 ms
Free fall
● IEC 61131-2:2017
In product packaging: 300 mm drop height
● IEC 60068-2-31:2008
● Test Ec, procedure 1
In shipping package: 1.0 m drop height
10.10 Electrical, EMC and climatic requirements
Article number 7MH4138-6BA00-0CU0
Product safety
Safety regula‐
tions
IEC 61010-1:2016
UL 61010-1:2012
IEC 61010-2-201:2013
IEC 61131-2:2017
UL 508:2003
CSA C22.2 No.142
Protection class IEC 61140:2016
IEC 61131-2:2017
To maintain the safety characteristics of extra-low voltage circuits, ex‐
ternal connections to communications ports, analog circuits, as well as
all 24 V DC nominal power supplies and all I/O circuits must be powered
by approved sources that fulfill the requirements according to the vari‐
ous standards for SELV, PELV, NEC Class 2, voltage limited or power
limited. The ground connection for the DIN rail serves as a functional
ground for dissipating interference currents.
IP degree of pro‐
tection
IEC 60529:2014 IP 20:
Protection against contact with standard probe
Protection against solid bodies with diameters in excess of 12.5 mm
No special protection against water
Technical data
10.10 Electrical, EMC and climatic requirements
Technology module TM SIWAREX WP351 HF