EasyManuals Logo

Siemens TM SIWAREX WP351 HF User Manual

Siemens TM SIWAREX WP351 HF
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #66 background imageLoading...
Page #66 background image
Example
Maximum weighing range= 100 kg
Maximum positive zeroing limit = 10%
→ Up to 10 kg (10% of 100 kg) can be set to zero by the function on power on.
6.5.21 Semi-automatic zero-setting device limit negative (% of max.)
[semiAutomaticZeroSettingLimitNegative]
Max. permissible negative deviation from the calibration zero point if the functions "Semi-
automatic zero-setting“ (command 21), "Automatic zero-setting device" and "Zero tracking
device" are used. The setting is made in % in reference to the maximum load of the weighing
range 1.
With scales requiring official calibration, the sum of the negative and positive limit value may not
exceed 4%.
Example
Max. weighing range = 100 kg
Maximum negative zeroing limit = 3%
→ Up to 3 kg (3% of 100 kg) can be set to zero by the zero setting functions.
6.5.22 Semi-automatic zero-setting device limit positive (% of max.)
[semiAutomaticZeroSettingLimitPositive]
Max. permissible positive deviation from the calibration zero point if the functions "Semi-
automatic zero-setting" (command 21), "Automatic zero-setting device" and "Zero tracking
device" are used. The setting is made in % in reference to the maximum load of the weighing
range 1.
With scales requiring official calibration, the sum of the negative and positive limit value may not
exceed 4%.
Example
Maximum weighing range = 100 kg
Maximum negative zeroing limit = 1%
→ Up to 1 kg (1% of 100 kg) can be set to zero by the zero setting functions.
6.5.23 Stability monitoring
The electronic weighing system monitors the weight for stability and reports the stability weight
via a status signal (stability 1 and 2). The stability monitoring is defined via the stability weight
and a stability time. The electronic weighing system uses the stability status as follows:
Stability 1: Must exist to start commands such as zeroing or taring.
Stability 2: Must exist to start automatic log printing, perform tolerance checks or totaling the
weight.
Parameter assignment/addressing
6.5 DR03 Calibration parameters
Technology module TM SIWAREX WP351 HF
66 Operating Instructions, 01/2020, A5E47521010-AA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens TM SIWAREX WP351 HF and is the answer not in the manual?

Siemens TM SIWAREX WP351 HF Specifications

General IconGeneral
BrandSiemens
ModelTM SIWAREX WP351 HF
CategoryControl Unit
LanguageEnglish

Related product manuals