User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
c) For a power,
– using the arrows in the top navigation bar, select any
logical channel
such as 22,
– in
Name
parameter write
Power
,
–
Mode
parameter set as
Math function
,
– press the button next to the
Function
label to select the appropriate function that
allows the calculation of the heater power P = I * U,
•
Function
parameter set as
X*Y
,
•
Type of source X
parameter set as
channel
,
•
Source X
parameter set as
logical channel 20
, which defined as a reading of
the heater current,
•
Type of source Y
parameter set as
channel
,
•
Source Y
parameter set as
logical channel 21
, which is defined as reading of
the heater voltage,
–
Scale
parameter set as
linear
,
– press
Configure scaling
button,
• in
Output unit
parameter write
kW
,
• in
Input value
parameter in the
Point 1
section write
0
,
• in
Output value
parameter in the
Point 1
section write
0kW
,
• in
Input value
parameter in the
Point 2
section write
1000
,
• in
Output value
parameter in the
Point 2
section write
1kW
,
– for
Displaying
block parameters:
•
Format
parameter set as
numeric
,
•
Precision
parameter set as
0.00
,
• in
Graph low
parameter write
0kW
,
• in
Graph high
parameter write
2kW
, (we assume that the value of heater power
consumption exceeds 2kW=5A*400V),
– all other parameters should be on default settings,
114