User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
The window with basic parameters of the
Profile/timer
shown on
Fig. 7.99
.
Fig. 7.99. View of the configuration Profiles/timers window
Arrows placed in the upper right corner of the screen allow you to switch
between Profile/timer. The middle button allows you to directly select a
specific Profile/timer from the list.
Common parameters for
Profile/timer
are:
Name
– it gives the name to the Profile/timer,
Triggering mode
using this parameter user select a way to generated
Profile/timer, there are five modes of triggering:
disabled
,
level (gate)
this means that
Profile
which was configured by user will be
generated when source signal will have a value > 0, otherwise (if source value
≤ 0) defined Profile will not be generated. For more details see
Chapter 7.12.2.
Profiles/timers - Triggering mode: level (gate), edge (once), edge (retrig.)
,
edge (once)
this means that which was configured by user
Profile
will be
triggered by rising edge signal (from values 0 to the value > 0) come from
source signal. After the rising edge the
Profile
will be generated in whole (once),
regardless of further changes to the signal source. For more details see
Chapter 7.12.2. Profiles/timers - Triggering mode: level (gate), edge (once),
edge (retrig.)
,
edge (retrig.)
- this means that configured by user
Profile
will be triggered by
rising edge signal (from values 0 to the value > 0) that comes from source
signal. However, in this mode, unlike the
edge (once)
mode a defined
Profile
will be generated from the beginning every time when the Triggering source
signal will generate an edge, whether that Profile had been completed or not.
For more details see
Chapter 7.12.2. Profiles/timers - Triggering mode: level
(gate), edge (once), edge (retrig.)
,
on time
in this mode the
Profile/timer
is generated in selected time (using
parameter
Triggering times
). For more details see
Chapter 7.12.3.
Profiles/timers - Triggering mode: on time
,
Pause mode
– way to pause generated Profile/timer,
disabled
– Profile/timer can not be paused,
high level
– Profile/timer will be paused, when channel's value in
Pause source
parameter will be greater than zero ( >0 ) and will be resumed when this value
will be lower or equal zero ( ≤0 ). If Profile/timer is paused and new trigger will be
175

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simex multicon cmc-99 and is the answer not in the manual?

Simex multicon cmc-99 Specifications

General IconGeneral
BrandSimex
Modelmulticon cmc-99
CategoryController
LanguageEnglish

Related product manuals