EasyManua.ls Logo

Simex multicon cmc-99 - Page 237

Simex multicon cmc-99
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Most important parameters of UI modules:
UI4 UI8 U16 I16
Number of inputs 4xU + 4xI 8xU + 8xI 16xU 16xI
Hardware limitations
voltage inputs
current inputs
0V ÷ 12V
0mA ÷ 24mA
0V ÷ 12V
0mA ÷ 24mA
0V ÷ 12V
-
-
0mA ÷ 24mA
Hardware resolution
voltage inputs
current inputs
1mV
1µA
1mV
1µA
1mV
-
-
1µA
Precision
voltage inputs
current inputs
0,1% @ 25˚C
0,1% @ 25˚C
0,1% @ 25˚C
0,1% @ 25˚C
0,1% @ 25˚C
-
-
0,1% @ 25˚C
Covered
MultiCon CMC-99/141
measurement ranges *
type max. type max. type max. type max.
0÷5V
1÷5V
0÷10V
2÷10V
0÷20mA
4÷20mA
0÷6V
0÷6V
0÷12V
0÷12V
0÷22mA
4÷22mA
0÷5V
1÷5V
0÷10V
2÷10V
0÷20mA
4÷20mA
0÷6V
0÷6V
0÷12V
0÷12V
0÷22mA
4÷22mA
0÷5V
1÷5V
0÷10V
2÷10V
-
-
0÷6V
0÷6V
0÷12V
0÷12V
-
-
-
-
-
-
0÷20mA
4÷20mA
-
-
-
-
0÷22mA
4÷22mA
Temperature stability
50 ppm/
˚
C 50 ppm/
˚
C 50 ppm/
˚
C 50 ppm/
˚
C
Internal impedance
voltage inputs
current inputs
50kΩ
type 100Ω
50kΩ
type 100Ω
50kΩ
-
-
type 100Ω
Protection
voltage inputs
current inputs
no
50mA auto-reset
fuse
no
50mA auto-reset
fuse
no
-
-
50mA auto-reset
fuse
Sampling period 10ms 10ms 10ms 10ms
Isolation strength 1 min. @ 500V AC 1 min. @ 500V AC 1 min. @ 500V AC 1 min. @ 500V AC
Weight 57 g 77 g 65 g 75 g
*
Measurement ranges are limited by software upon hardware inputs ability, check current list of
MultiCon CMC-99/141
measurement ranges at producer's website
Tab. 8.2 Technical data for the module UI4, UI8, U16, I16
237

Table of Contents