User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
type
range* resolution full range full range accuracy limited range
limited range
accuracy
[ mV ] [ μV ] [
°C
] [
°C
] [ % ] [
°C
] [
°C
] [ % ]
K
-10÷120 4 -200÷1370 ±8 ±0.51 -100÷1370 ±4 ±0.27
S
-10÷30 2 -50÷1768 ±7.5 ±0.41 0÷1768 ±6 ±0.34
J
-10÷120 4 -210÷1200 ±6.3 ±0.44 -100÷1200 ±3 ±0.23
T
-10÷30 2 -200÷400 ±1.9 ±0.31 -100÷400 ±1 ±0.20
N
-10÷120 4 -200÷1300 ±12 ±0.80 -100÷1300 ±5,9 ±0.42
R
-10÷30 2 -50÷1768 ±8.6 ±0.47 0÷1768 ±5,5 ±0.31
E
-10÷120 4 -200÷1000 ±4.7 ±0.40 -100÷1000 ±2,7 ±0.25
L
-10÷120 4 -200÷800 ±4.4 ±0.44 -100÷800 ±2,5 ±0.28
B
-10÷30 2 250÷1820 ±15 ±0.96 480÷1820 ±6 ±0.45
C
-10÷120 4 50÷2290 ±13 ±0,51 50÷1900 ±9,2 ±0,5
* with consideration of device working in -20'C÷50'C of ambient temperature.
Tab. 8.14 Thermocouple measurement accuracy for the UN3 and UN5 modules
type norm
K
PN-EN 60584-1:2014
S
PN-EN 60584-1:2014
J
PN-EN 60584-1:2014
T
PN-EN 60584-1:2014
N
PN-EN 60584-1:2014
R
PN-EN 60584-1:2014
E
PN-EN 60584-1:2014
L
GOST R 8.595:2004
B
PN-EN 60584-1:2014
C
PN-EN 60584-1:2014
Tab. 8.15 Thermocouple norm for the UN3 and UN5 modules
258