USER MANUAL « ASP 116 EVOLUTION »
Sprinte SAS, All rights reserved, including translation rights
2.12.8.2 Boost managment
CONFIGURATION ► FREQ. INVERTER ► ASYNC. OPTIMIZ. ► BOOST
Adjustment of the motor magnetizing current at low speed, as a % of the rated
magnetizing current. This parameter is used to increase or reduce the time taken to
establish the torque. It allows gradual adjustment up to the frequency set by “Action
Boost”.
Frequency above which the magnetizing current is no longer affected by BOOST
2.12.9 Inspection mode
CONFIGURATION ► FREQ. INVERTER ► INSPECTION MODE
Value of the "inspection" mode frequency reference. (ISRF)
Time to accelerate from 0 to the inspection speed.
Make sure that this value is compatible with the inertia being driven.
2.12.10 Electric noise reduction
CONFIGURATION ► FREQ. INVERTER ► NOISE LEVEL
Switching freq.
Switching frequency setting.
[0..16] KHz (8 KHz by default)
Random frequency modulation prevents any resonance, which may occur at a fixed
frequency.