USER MANUAL « ASP 116 EVOLUTION »
CONFIGURATION
Sprinte SAS, All rights reserved, including translation rights
32
2.15 Building
SETUP BUILDING
LEVELS NUMBER
Number of levels served by lift
[2..32] Adjustable from 2 to 32 level
MAIN LEVEL
Main level
On Collective, the landing buttons below the main level are “up land” and the other
landing buttons “down land”. The car goes back to main level in case of fire operation
[0..31] This setting is reset to zero if it is higher than the numbers of levels.
GAPS LEVELS
Management of gaps levels for bank of lifts (multiplex)
.
The elevator that going down to the lowest level will have GAPS LEVELS = 0.
Other lifts that can not going down to the lowest level indicates the number of levels
they cannot serve with this parameter.
Example of a duplex:
The elevator that has 3 subsoil has GAPS LEVELS = 0
The elevator that has 1 subsoil has GAPS LEVELS = 2
The levels of the landings buttons are configured by referring to the elevator coming
down the lowest.
Levels of the car buttons are configured as a simplex
[0..31]
RETURN TO FLOOR
Return to a dedicated floor after a waiting time
[NO] [YES]
TIME STOP FLOOR
Waiting time before the car returns to its stopped floor
[0..20] minutes
STOPPED FLOOR
Level of the stopped floor
In hydraulic, the stopped floor is obligatory the lowest.
[0..31]
‘OUT OF USE’ LVL
Level of the ‘Out of Use’ operation
When this operation is activated , the lift will park at this floor.
[0..31]
OOU.DOORS OPENED
Parking doors opened in ‘Out Of Use’ operation
[NO] [YES]
CAR BLOCK TIMER
Detection time of a blocked lift
Maximum time limit for taking calls into account. If the lift has calls waiting and the time
expires, then the lift is put into blocked state.
In this state, car sending and landing calls in progress are erased to warn the users
that the car will not be coming. In multiplex, is excluded from the bank. If the cause of
the blocking disappears and a new call is made, this will be responded to.
[1..20] minutes (4 minutes by default)