2.10.2 Standard configuration
Timing to detect a no movement of the car
Maximum car movement time without having information from position reader. Once
time is passed, the lift is faulty.
This security is deactivated in INSPECTION mode and LEVELLING mode
224SP : [10..20] seconds (20 sec by default)
K04SP/K05SP : [01..05] seconds (5 sec by default)
maximum authorized acceleration of the car measured by K04SP / K05SP
[0..2,5] m.s2 (2,5 sec by default)
« 0 » value disables the function
Maximum low speed movement lift in normal service
[10..20] seconds (20 s by default)
Type of thermal protection of the traction machine
Use the input CN12I-ST / 220SP
[NO PROBE] [RESISTIVE PROBE] [DRY CONTACT]*
2.11 Automatic evacuation
CONFIGURATION ► RESCUE (only available with ATV 71L BUS inverter type )
Automatic evacuation of passengers in case of main power failure.
In this case, the ATV71L BUS inverter is able to move the car to the nearest floor,
choosing the easiest direction.
[BY RELAY]: Rescue is launched by a timer relay.
Car speed in evacuation operation
This setting is transmitted to the inverter when moving in evacuation operation.
Unit is in Hertz