2.10 Hoist mechanism
SETUP ► HOIST
[ELECTRIC VVF] [HYDRAULIC] [ELECTRIC 1V] [ELECTRIC 2V]
Type of frequency inverter
[ADL300 M-SPEED] [Z.A. ZETADYN] [ALTIVAR ATV71L] [ATV71L BUS]
Selection of movement speed during inspection
[LOW SPEED]* [HIGH SPEED]
[POSITIV DRV LIFT] [FRICTION LIFT] [GEARLESS MOTOR]
Timing delay of the release of line contactors
Adjustment of time limit to release the line contactors , see control timing chart next
page
[0.4..4] seconds (1,5 s by default)
Monitoring of the wear of plastic sheathed ropes
The plastic sheathed ropes have to be replaced after a maximum number of direction
changes of the car (see below to adjust this number).
You have to activate this function if your lift is equipped with these ropes
Maximum number of direction changes (for rope wear).
Ask the ropes supplier to set the correct value.
Every direction changes of the car is counted to monitor the wear of plastic sheathed
ropes..
Once the maximum value set here is reached, the Lift falls out of order and you have
to replace the ropes. A warning is reported at 95% of this max value (see §4.4.10).
The current value of the counter is visible in the DIAGNOSIS->STATISTICS menu
(cf§4.3). When ropes have been replaced, reset this value to 0.
Inspection speed must not exceed 0.63 m/sec