MANUEL D’UTILISATION « ASP 116 EVOLUTION »
MAINTENANCE
Sprinte SAS, All rights reserved, including translation rights
63
The writing of parameters file failed and is not possible anymore.
The Lift is still working but it’s not possible to modify any settings.
- Change the SD card and contact our AfterSales department in order to recover your files.
ALARM
FILE OPEN
Parameter file is unreadable
The controller’s parameter file is unreadable or not present on the SD card.
The Lift is still working but it’s not possible to modify any settings.
- Change the SD card and contact our AfterSales department in order to recover your files.
ALARM
CONFIG VERSION
Invalid parametre file
The controller’s parameter file is not compatible with the software version of the controller.
The Lift is still working but it’s not possible to modify any settings.
- Change the SD card and contact our AfterSales department in order to recover your files.
OO
CONFIG SDCARSD
Configuration fault
No valid configuration exists in the controller (nor in memory neither on SDcard). The controller and so the lift
can’t operate.
- Change the SD card and contact our AfterSales department in order to recover your files.
ALARM
DIAL LIFT. N°XX
Error on CAN multiplex communication
The “CAN” communication between the control panels is not operating correctly. The lifts can operate in
multiplex.
- Check the CN7M / 216SP and CN8M / 216SP connectors
- Check the that the cable is not near from a power cable
ALARM
MULTIPLEX NUMB
Error of the lift identification on the multiplex bus
At least, 2 lifts have the same lift number
- Modify the number of one lift in the menu IDENTIFICATION
ALARM
CLOCK OFF
The 216SP board’s clock is not working
- Change the 216SP board
ALARM
CLOCK SETTING
The clock is not set.
- Please set time and date in the CONFIGURATION -> CONTROL PANEL
ALARM
MISSING SD 211
La SD card of 211SP board (car roof) is missing.
Therefore vocal messages can't be broadcasted anymore.
- Check if the SD card is present and properly inserted.
- Otehrwise, replace the SDcard
ALARM
211 INIT AUDIO
The audio system of 211SP had to be reinitialized
An audio file could not be broadcast, the problem has been detected and corrected by the 211SP card.
This defect is just informative, everything works as before.
ALARM
SECU SOFTW XX
Software security
This fault is a software security.
- Make a reset and inform our After Sales department.
OO
DBD SWITCHED ON
Door Bypass Device was engaged
This device is engaged and therefore , the lift can’t operate in normal user mode. Only emergency recall
operation and inspection mode are allowed)