MANUEL D’UTILISATION « ASP 116 EVOLUTION »
MAINTENANCE
Sprinte SAS, All rights reserved, including translation rights
65
- Make a new software update of the control panel
ALARM
REPROG BOARD N°XX
Software upgrade error of a floor board
The software upgrade of floor board N°XX didn’t ended properly
- Try once again a new software upgrade
- Change the board
ALARM
SAME ID N°XX
Two floor boards have the same identifier
- Modify the switches position of the floor boards
ALARM
COMM. FLEXYPAGE #X
Communication error with flexyPage (#1 or #2)
- Check the CAN bus connection of the flexyPage
ALARM
COMM. PIT INSPEC.
Communication error with the pit inspection board 137SP
The 216SP board met some communication error with a the pit inspection board 137SP
- Verify the connectors
- Change the 137SP board
ALARM
VERS. PIT INSPEC.
Wrong software version of the pit inspection board 137SP
The software version of the pit inspection board 137SP is not compatible with the control panel software.
- Try once again a new software upgrade
ALARM
PROG. PIT INSPEC.
Software upgrade error of the pit inspection board 137SP
The software upgrade of the pit inspection board 137SP didn’t ended properly
- Try once again a new software upgrade
- Change the board
ALARM
ID. PIT INSPEC.
Two boards have the identifier of the pit inspection board
137SP
- Check the DIPs of the floor boards.
- Only one shall have ID number #27. (ID number dedicated to the pit inspection board 137SP).