4-28
4.3 Parameter Function Description
00 - Basic Parameters Group
00- 00 Control Mode Selection
Range
【0】:V/F Mode
【1】:Vector Mode
To select the appropriate vector or V/F control mode according to the load characteristics.
If V/F mode is selected, please set parameters, group1 to comply with the load features.
Vector is best suited to control the general load or rapidly-changed torque load.
00- 02 Main Run Command Source Selection
Range
【0】:Keypad
【1】:External Run/Stop Control
【2】:Communication
【3】:PLC
Parameter 00 - 02 sets the inverter operation command source. For switching between 00-02 and
00-03,use any of the external inputs S1 to S6 and set the relavent parameters (03-00~03-05) to【12】.
Refer to parameter group3 for details.
※
Note: 00- 02=【3】, RUN key: Enable the built-in PLC run operation; STOP key: Enable the built-in PLC
stop operation.
00- 03 Alternative Run Command Source Selection
Range
【0】:Keypad
【1】:External Run/Stop Control
【2】:Communication
Parameter 00- 03 sets the inverter Alternative Run operation source. For switching between 00-02
and 00-03,use any of the external inputs S1 to S6 and set the relavent parameter (03-00~03-05) to
【12】. Refer to parameter group3 for details.
00- 04 Operation Modes for External Terminals
Range
【0】:Forward/Stop-Reverse/Stop
【1】:Run/Stop- Reverse/ Forward
【2】:3 Wire Control Mode - Run/Stop
00-04 is valid when run command is set to external mode by 00- 02/00- 03 =1.
2 Wire Operation Mode,
Set 00-04=【0/1】first, before setting (03-00,03-04) to【0】or【1】
00- 04=【0】, Set external terminals (03-00 to 03-05) function to 0 for FWD/Stop or Set to 1 for REV/Stop..
00- 04=【1】, Set external terminals (03-00 to 03-05) function to 0 for Run/Stop or Set to 1 for FWD/REV
3 Wire Operation Mode,
00-04 =【2】Terminals S1, S2, S3 are used in a combination to enable 3 wire run/stop mode.
Settings for 03-00, 03-01,03–02 will not be effective..(refer to group 03)
00- 05 Main Frequency Command Source Selection
00- 06 Alternative Frequency Command Source Selection
Range
【0】:Up/Down of Keypad
【1】:Potentiometer on Keypad
【2】:External AI1 Analog Signal Input
【3】:External AI2 Analog Signal Input
【4】:External Up/Down Frequency Control
【5】:Communication Setting Frequency
【6】:PID Output Frequency
【7】:Pulse Input
Parameter 00 - 05/00- 06 sets the inverter frequency command source.
When 00-05/00-06 =【6】, frequency command source is output of the PID.
※
Note: 00-05 ( Main Frequency Command Source) and 00- 06 (Alternative Frequency Command Source)